VDO SENSORS - FOR ENGINE MANAGEMENT V3.0 Bedienungsanleitung Seite 27

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 54
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 26
DSE Model 5110 Automatic Start Engine Management Instrumentation System
Part No. 057-009 5110 Operating Manual Issue 3.3 3/1/2006 27
CONFIGURABLE OUTPUTS (CONTINUED)
Factory default settings are in bold italicised text.
Parameter Selection
28 – Output 3 0 - Unused
1 - Preheat mode 0
2 - Air flap
3 - Load transfer
4 - Energise to stop
5 - Engine running
6 - Shutdown alarm
7 - System in auto
8 - Auxiliary input 1 active
9 - Auxiliary input 2 active
10 - Auxiliary input 3 active
11 - Auxiliary input 4 active
12 - Auxiliary input 5 active
13 - Preheat mode 1
14 - Preheat mode 2
15 - Preheat mode 3
16 - Warning alarm
17 - Common alarm
NOTE:- The ‘preheat modes’ selectable for configurable outputs and LCD indicators perform the following actions :
Preheat mode 0 - Preheat during preheat timer, ceasing at end of preheat timer.
Preheat mode 1 - Preheat during preheat timer and continue until engine stops cranking.
Preheat mode 2 - Preheat during preheat timer and continue until the safety delay timer has expired.
Preheat mode 3 - Preheat during preheat timer and continue until the warming timer has expired.
In addition, in all preheat modes, preheat takes place during the crank rest timer between crank cycles.
Seitenansicht 26
1 2 ... 22 23 24 25 26 27 28 29 30 31 32 ... 53 54

Kommentare zu diesen Handbüchern

Keine Kommentare